Alarms Configuration for OPC

To configure workstation alarms for a point, the following fields are available in a CSV configuration file:

For a detailed description of these fields, see OPC Items Data.

After you import an OPC configuration file, you can configure workstation alarms for individual OPC points from the Alarm Configuration expander in the Object Configurator tab (see Alarm Configuration).

Supported Alarm Type Operators

Alarm Type Operator

Operand

Meaning

Applicable Alarm Category

EQ

=

equal to

Discrete

NE

!=

not equal to

Discrete

LT

<

less then

Continuous

LE

<=

less than or equal to

Continuous

GT

>

greater than

Continuous

GE

>=

greater than or equal to

Continuous

BET

..

between

Discrete

NBET

!..

not between

Discrete

Note that:

Examples of Alarm Configuration

After the import of a CSV file:

Alarm Configuration in the CSV File

Configuration imported into the Alarm Configuration expander

[Alarm Class]; Alarm

Alarm Class: Alarm

[Alarm Type]: EQ

[Alarm Value]: 1

Value Range: = (1)

[Event Text]: Binary Input

Event Text: Boolean Alarm

[Normal Text]: Normal

Normal Text: Normal

 

Alarms Configuration in the CSV File

Configuration imported in the Alarm Configuration expander

[Alarm Class]; Alarm$Fault

Alarm Class: Alarm, Fault

[Alarm Type]: EQ$BET

[Alarm Value]: 10$[12$15]

Alarm Value Range: = 10

Fault Value Range: = 12 to 15

[Event Text]: Analog Alarm$Fault Alarm

Alarm Event Text: Analog Alarm

Fault Event Text: Fault Alarm

[Normal Text]: No Alarm$No Fault

Alarm Normal Text: No Alarm

Alarm Normal Text: No Fault