[Example] Using SiPass Cardholder Properties to Trigger a Reaction
On a management platform that integrates SiPass access control, you want to automate certain actions (for example, unlock a door, disarm the intrusion area, activate a fan coil, or turn on the desk light) when a specific person badges through. To do this, you will configure a reaction (requires a license) that is triggered by SiPass cardholder properties.
- Desigo CC is configured to integrate a SiPass access control system.
- System Manager is in Engineering mode.
- In System Browser, select Application View.
- Select Applications > Logics > Reactions.
- The Reaction Editor tab displays.
- From the Triggers expander, open the Values and States expander.
- In System Browser, select the Manual navigation check box.
- Select Management View, then navigate to Field Networks > … > [door with reader].
- Drag-and-drop the door with reader object into the empty area of the Target column in the Values and States expander.
- A new row is created for this target object.
- Configure the newly created row as follows:
- In the Property column, select Cardholder Transaction Reader 1 from the drop-down list.
- In the Value Range column, select the relational operator = and then select [Access Granted to Area].
- The first row will evaluate to True when there is an access granted transaction on this door reader.
- Drag-and-drop the same door with reader object into the empty area of the Target column, under the previously-configured row.
- A second row is created for the same target object.
- Configure the second row as follows:
- In the Property column, select Cardholder ID Reader 1 from the drop-down list.
- In the Value Range column, select the relational operator = and then enter the badge number of the person you want to admit.
- The second row will evaluate to True when the door reads this particular person’s badge.
- Select the All rows must be true radio button.
- The Values and States expander as a whole will evaluate to True when the door grants access to the specified cardholder.
- From the Output expander, open the Action expander.
- In System Browser, navigate to Field Networks > … > [door to unlock].
- Drag-and-drop the door to unlock object into the empty area of the Scope/Target column in the Action expander.
- A new row is created for this target object.
- Configure the newly created row as follows:
- In the Property column, select Latch State from the drop-down list.
- In the Command column, select Execute and enter the value Unlocked.
- The row is now configured to unlock the specified door latch when the reaction is triggered.
- Click Save As .
- In the Save Object As dialog box, select the main Reactions folder or any subfolder under it as the destination where you want to save this reaction:
a. In the Name field, enter a name for the reaction.
b. Click OK.
- The new reaction object is available in System Browser, and is enabled by default.
Related Topics
Reaction Editor Reference
Input Triggers of a Reaction
Output Instructions of a Reaction