Migrating or Upgrading SPC

You can directly upgrade to V7 from V5.0 or higher. To upgrade from older Desigo CC versions, you must upgrade through intermediate steps. See the instructions below.

NOTE: The Danger Management Propagation extension is no longer supported in Desigo CC V7. If you are upgrading a project that included this extension, you must remove the extension either before or immediately after upgrading to V7. In addition, any macros, reactions or scripts that relied on propagated properties will have to be reworked.

Upgrading Desigo CC with SPC to V7

  • From Desigo CC V5.x or V6.x, just follow the standard Desigo CC upgrade procedure for V7 .
  • From older versions, you must first upgrade to V5.x or V6.x (see instructions below), and then follow the standard Desigo CC upgrade procedure for V7.

Upgrading Desigo CC with SPC to V5.x or V6.x

  • From Desigo CC V4.x, follow the standard Desigo CC upgrade procedure for V5.x or V6.x .
  • From Desigo CC V3.x, follow the standard Desigo CC upgrade procedure for V5.x.
  • From Desigo CC V2.x, you must first upgrade to V3.x or V4.x, and then follow the standard Desigo CC upgrade procedure for V5.x or V6.x.
  • From Desigo CC V1.x you must first upgrade to V3.x, and then follow the standard Desigo CC upgrade procedure for V5.x.

Upgrading SPC Panel from Earlier version or Protocol Change (EDP to FlexC)

A new import of the SPC configuration file is required.

Migrating from Sintony to SPC Intrusion System

You can replace Sintony panels with SPC panels without affecting the field network. Sintony detection lines and peripheral devices do not need to be replaced. In fact, the SPC control panels can connect to existing Sintony lines via the dedicated hardware module SPC E-bus Gateway (SPCG310).

  • For more information about characteristics and limitations of the Sintony migration path, refer to the Sintony System Migration white paper (December 2013).

The management platform supports the SPC E-bus Gateways and the connected lines, which will appear in Desigo CC as SPC objects.

In Desigo CC projects, Sintony configurations cannot be reused after the migration to SPC. In case you need to modify a project and replace a Sintony with SPC, proceed as follows:

  1. Take note of the Sintony intrusion configuration in Desigo CC, including graphics, event handling operating procedures, automatic reactions, and so on.
  2. Remove the Sintony panel.
  3. Create a new SPC panel.
  4. Import the SPC configuration that includes SPC E-bus gateways and lines.
  5. Following your notes, configure the SPC intrusion subsystem as required.