Advantronic AD300 Compatibility and System Limits

Compatibility

  • Desigo CC V3.0 or higher

Size Limits

Since no specific limits are identified for this integration, refer to Desigo CC system limits defined in the System Description document (A6V10415500).

Other Limitations

  • Due to a limitation in the Desigo CC Modbus integration, the event commands (Ack and Reset) are available for the system object only. They cannot be replicated in the Operation tab for panel and detectors elements.
  • When a panel or detector event occurs, the Ack and Reset commands become available in Event List with the following limitations for the current version:
    • The Ack and Reset commands are both available at the same time. They remain available also when the acknowledge command has been successfully executed.
    • The event blinks constantly, also after the Ack command has been successfully executed.
    • In order to have the Ack and Reset commands to work in Event List, a specific configuration step in the Desigo CC station is required. For instructions, see Configuring Advantronic AD300 Event Commands Macros.