Modifying the Notifier ID 3000 Communication Settings

When integrating a NOTIFIER® ID3000 fire panel, after the import of the configuration file, you can modify the communication settings (TCP port and IP address) of the communication interface.

  • System Manager is in Engineering mode.
  1. In System Browser, select Management View.
  1. Select Project > Field Networks > [ID3000 network] > [Notifier ID3000 interface].
  1. In the Modbus tab, open the Communication Interface expander.
  1. Modify the values in the fields TCP port or IP address.
  1. Click Save .
Communication Settings of the Interface