SecuriFire BACnet Integration
This integration permits the user to access objects from corresponding SecuriFire devices and monitor them from Desigo CC.
Safety functions
Observe all applicable standards for the country as well as regional or local regulations when integrating safety functions.
Dependencies
The Securiton SecuriFire extension is configured to depend on the following extension, which will be automatically added, if it is not already installed in the system, when the Securiton SecuriFire installation feature is selected:
- Fire Domain Libraries Common
To be able to work with EDE files, you must manually add the following extension:
- Desigo System (Core)
Engineering for SecuriFire BACnet System
SecuriFire BACnet systems can be integrated into Desigo CC in one of the following ways:
- Online engineering. In online mode, the panel must be connected to the management station and from there you can start the discovery of the devices online data. For instructions, see Integrating SecuriFire BACnet System Through Online Discovery.
- Offline mode. In offline configuration, you prepare an Engineering Data Exchange (EDE) file that contains BACnet devices project data and then you import the configuration. For instructions, see Integrating SecuriFire BACnet System Through Offline Configuration.
Before performing the online discovery or offline configuration, a BACnet driver and network must be created.
Type of Configuration | Engineering | Advantage | Disadvantage |
Online discovery | For online engineering, Desigo CC is connected to the devices and you perform an online discovery of project data. |
|
|
Offline import | For offline engineering, you must edit and import an Engineering Data Exchange (EDE). An online connection with the BACnet device is not required. |
|
|
Supported Object Types
Both online discovery and offline import support standard BACnet objects only. This means that BACnet extensions made by the manufacturer are not supported by these Desigo CC features. The current version supports the defined BACnet objects in the following library: Project > System settings > Libraries > Fire (HQ) > Devices > BACnet > Object models.
Object Models and Object Types in the Library Fire_Device_BACnet_HQ_1 | ||
Object Model | Short Name | Full Name |
GMS_BACNET_SecuriFire EO_FI_DEV_150 | DEV | Device |
GMS_BACNET_SecuriFire EO_FI_LSP_150 | LSP | Life Safety Point |
GMS_BACNET_SecuriFire EO_FI_LSZ_150 | LSZ | Life Safety Zone |
GMS_BACNET_SecuriFire EO_FI_MSV_150 | MSV | Multi-State Value |
GMS_BACNET_SecuriFire EO_FI_MSV_LS_150 | MSV_LS | Multi-State Value Life Safety |
GMS_BACNET_SecuriFire EO_FI_NC_150 | NC | Notification Class |
Supported EoTypes and Functions from EDE File
The EDE file contains a list of items where you can set a specific Function and EoType for fire objects.
See an example below. For details, see SecuriFire EDE File Formats.
#Engineering-Data-Exchange;;;;;;;;;;;;;;;
PROJECT_NAME;Standard Project;;;;;;;;;;;;;;
VERSION_OF_REFERENCEFILE;1;;;;;;;;;;;;;;
TIMESTAMP_OF_LAST_CHANGE;06.06.2019;;;;;;;;;;;;;;
AUTHOR_OF_LAST_CHANGE;;;;;;;;;;;;;;;
VERSION_OF_LAYOUT;2;;;;;;;;;;;;;;
#mandatory;mandatory;mandatory;mandatory;mandatory;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional
# keyname;device obj.-instance;object-name;object-type;object-instance;description;min-present-value;max-present-value;commandable;hi-limit;low-limit;state-text-reference;unit-code;function;resolution;EoType
Device(1);1;CSF_1;8;1;SecuriFire Client;;;;;;;;;;EO_FI_DEV
MultistateValue(61);1;CSF_1_LOC_1_MDA_24;19;61;;;;N;;;1;;;;EO_FI_MSV
MultistateValue(60);1;CSF_1_ZO_2_DET_1;19;60;Melder Zeile 2 Zeile 3 Objekttext Information;;;N;;;2;;;;EO_FI_MSV
MultistateValue(59);1;CSF_1_ZO_1_DET_1;19;59;Melder Zeile 2 Zeile 3 Objekttext Information;;;N;;;2;;;;EO_FI_MSV
MultistateValue(58);1;CSF_1_ZO_2;19;58;Meldergruppe;;;N;;;2;;AutDet;;EO_FI_MSV
MultistateValue(57);1;CSF_1_ZO_1;19;57;Melderguppe;;;N;;;2;;;;EO_FI_MSV
MultistateValue(56);1;CSF_1_OUT_4_ACK;19;56;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(55);1;CSF_1_OUT_3_ACK;19;55;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(54);1;CSF_1_MS_2;19;54;;;;N;;;4;;;;EO_FI_MSV
MultistateValue(53);1;CSF_1_CO_2;19;53;;;;N;;;5;;;;EO_FI_MSV
MultistateValue(52);1;CSF_1_EX_2;19;52;Extern;;;N;;;6;;;;EO_FI_MSV
MultistateValue(51);1;CSF_1_OUT_4;19;51;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(50);1;CSF_1_OUT_3;19;50;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(49);1;CSF_1_IN_2;19;49;Aktiv;;;N;;;7;;;;EO_FI_MSV
MultistateValue(48);1;CSF_1_IN_1;19;48;Aktiv;;;N;;;7;;;;EO_FI_MSV
MultistateValue(47);1;CSF_1_CI_2_OP;19;47;Bediengerät;;;N;;;8;;;;EO_FI_MSV
MultistateValue(46);1;CSF_1_CI_1_OP;19;46;Bediengerät;;;N;;;8;;;;EO_FI_MSV
MultistateValue(45);1;CSF_1_OUT_2_ACK;19;45;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(44);1;CSF_1_OUT_1_ACK;19;44;Ausgang;;;N;;;3;;;;EO_FI_MSV
MultistateValue(43);1;CSF_1_LO_1_LL;19;43;Ring;;;N;;;9;;;;EO_FI_MSV
MultistateValue(42);1;CSF_1_DL_1_AT;19;42;;;;N;;;10;;;;EO_FI_MSV
MultistateValue(41);1;CSF_1_CI_2_AC;19;41;Bediengerät;;;N;;;8;;;;EO_FI_MSV
MultistateValue(40);1;CSF_1_CI_1_AC;19;40;Bediengerät;;;N;;;8;;;;EO_FI_MSV
MultistateValue(39);1;CSF_1_MA_65535;19;39;;;;N;;;11;;;;EO_FI_MSV
MultistateValue(38);1;CSF_1_LO_1;19;38;Ring;;;N;;;9;;;;EO_FI_MSV