Enabling the Signify Occupancy Alarm

You can enable the alarm for one or all the Occupancy sensors.

  1. In System Browser, in the Signify SORIS network, select the Occupancy Sensor whose alarm you want to enable.
    NOTE: For a general modification, affecting all sensors, select the GMS_Signify_OccupacySensor_150 object model in the Signify library.
  2. In the Object Configurator tab, close the Main expander and open the Properties expander.
  3. In the list on the left, select the Status property.
  4. The Details, Alarm Configuration and other expanders on the right update to show the settings of the selected property.
  5. In the Alarm Configuration expander:
    a. Set the Valid field so it displays a gray (not blue) checkmark.
    b. Select the Alarm config.activated check box.
  6. Click Save .
  1. The alarm for the Occupied status is now enabled.