Honeywell Esser Integration
This integration permits the user to access objects from corresponding Honeywell Esser devices and monitor them from Desigo CC.

Safety functions
Observe all applicable standards for the country as well as regional or local regulations when integrating safety functions.
Dependencies
The Honeywell Esser extension is configured to depend on the following extension, which will be automatically added, if it is not already installed in the system, when the Honeywell Esser installation feature is selected:
- DMS Common

To be able to work with EDE files, you must manually add the following extension:
- Desigo System (Core)
Engineering for Honeywell Esser Fire System
The Honeywell Esser fire system can be integrated into Desigo CC in one of the following ways:
- Online engineering. In online mode, the panel must be connected to the management station and from there you can start the discovery of the devices online data. For instructions, see Integrating the Esser Fire System Through Online Discovery.
- Offline mode. In offline configuration, you prepare an Engineering Data Exchange (EDE) file that contains BACnet devices project data and then you import the configuration. For instructions, see Integrating the Esser Fire System Through Offline Configuration.
Before performing the online discovery or offline configuration, a BACnet driver and network must be created.
Type of Configuration | Engineering | Advantage | Disadvantage |
Online discovery | For online engineering, Desigo CC is connected to the devices and you perform an online discovery of project data. |
|
|
Offline import | For offline engineering, you must edit and import an Engineering Data Exchange (EDE). An online connection with the BACnet device is not required. |
|
|
Supported Object Types
Both online discovery and offline import support standard BACnet objects only. This means that BACnet extensions made by the manufacturer are not supported by these Desigo CC features. The current version supports the defined BACnet objects in the following library: Project > System settings > Libraries > Fire (HQ) > Devices > BACnet > Object models.
Object Models and Object Types in the Library Fire_Device_Esser_150_HQ_1 | ||
Object Model | Short Name | Full Name |
GMS_BACnet_Esser_EO_FI_ACU_150 | ACU | Acusting |
GMS_BACnet_Esser_EO_FI_CMDPAN_150 | CMDPAN | Command Panel |
GMS_BACnet_Esser_EO_FI_CON_150 | CON | Connection |
GMS_BACnet_Esser_EO_FI_DISFP_150 | DISFP | Disconnect Fire Point Command |
GMS_BACnet_Esser_EO_FI_FP_150 | FP | Fire Point |
GMS_BACnet_Esser_EO_FI_GW_150 | GW | Gateway |
GMS_BACnet_Esser_EO_FI_LN_150 | LN | Line |
GMS_BACnet_Esser_EO_FI_NC_150 | NC | Notification Class |
GMS_BACnet_Esser_EO_FI_OUT_150 | OUT | Output |
GMS_BACnet_Esser_EO_FI_PAN_150 | PAN | Panel |
GMS_BACnet_Esser_EO_FI_UE_150 | UE | UE |
Supported EoTypes and Functions from EDE File
The EDE file contains a list of items where you can set a specific Function and EoType for fire objects.
See an example below. For details, see Honeywell Esser EDE File Formats.
#Engineering-Data-Exchange. Template example for ESSER integration;;;;;;;;;;;;;;;;;
VERSION_OF_LAYOUT;2;;;;;;;;;;;;;;;;
#mandatory;mandatory;mandatory;mandatory;mandatory;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional
#keyname;device obj.-instance;object-name;object-type;object-instance;description;present-value-default;min-present-value;max-present-value;commandable;supports COV;hi-limit;low-limit;state-text-reference;unit-code;state-text;function;EoType
#;;;;;;;;;;;;;;;;;
# Parent Hierarchy levels;;;;;;;;;;;;;;;;;
Detection;1211;Esser'Detection;999;10002;Building;;;;;;;;;;;;Esser_EO_FI_AGG
Detection'Group1;1211;Esser'Detection'Group1;999;10003;Floor1;;;;;;;;;;;Automatic_Group;Esser_EO_FI_AGG
Detection'Group1'Element1;1211;Esser'Detection'Group1'Element1;999;10004;Room1;;;;;;;;;;;Automatic_Element;Esser_EO_FI_AGG
Detection'Group1'Element2;1211;Esser'Detection'Group1'Element2;999;10005;Room2;;;;;;;;;;;Automatic_Element;Esser_EO_FI_AGG
Detection'Group3;1211;Esser'Detection'Group3;999;10006;Floor3;;;;;;;;;;;Manual_Group;Esser_EO_FI_AGG
Detection'Group3'Element1;1211;Esser'Detection'Group3'Element1;999;10007;Room3;;;;;;;;;;;Manual_Element;Esser_EO_FI_AGG
Detection'Outputs;1211;Esser'Detection'Outputs;999;10009;Control Outputs;;;;;;;;;;;;Esser_EO_FI_AGG
#;;;;;;;;;;;;;;;;;
BACnet-ESSER;1211;BACnet-ESSER;8;1211;-;;;;;;;;;;;;Esser_EO_FI_GW
Detection'Group1'OBJECT_MULTI_STATE_VALUE:2;1211;T1_G0001_E00;19;2;GROUP 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP
Detection'Group3'OBJECT_MULTI_STATE_VALUE:4;1211;T1_G0003_E00;19;4;GROUP 3;;;;;;;;;;;FirePoint;Esser_EO_FI_FP
Detection'Group3'OBJECT_MULTI_STATE_OUTPUT:103;1211;T7_G0003_E00;14;103;CONNECT/DISCONNECT GROUP 3;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP
Detection'Group1'OBJECT_MULTI_STATE_OUTPUT:101;1211;T7_G0001_E00;14;101;CONNECT/DISCONNECT GROUP 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:22;1211;T2_G0011_E00;19;22;OUTPUT 11;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:23;1211;T2_G0012_E00;19;23;OUTPUT 12;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:24;1211;T2_G0013_E00;19;24;OUTPUT 13;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:25;1211;T2_G0014_E00;19;25;OUTPUT 14;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:26;1211;T2_G0015_E00;19;26;OUTPUT 15;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Outputs'OBJECT_MULTI_STATE_VALUE:27;1211;T2_G0016_E00;19;27;OUTPUT 16;;;;;;;;;;;Output;Esser_EO_FI_OUT
Detection'Group1'Element1'OBJECT_MULTI_STATE_VALUE:12;1211;T1_G0001_E01;19;12;GROUP 1 ELEMENT 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP
Detection'Group1'Element2'OBJECT_MULTI_STATE_VALUE:13;1211;T1_G0001_E02;19;13;GROUP 1 ELEMENT 2;;;;;;;;;;;FirePoint;Esser_EO_FI_FP
Detection'Group3'Element1'OBJECT_MULTI_STATE_VALUE:18;1211;T1_G0003_E01;19;18;GROUP 3 ELEMENT 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP
Detection'Group1'Element1'OBJECT_MULTI_STATE_OUTPUT:111;1211;T7_G0001_E01;14;111;CONNECT/DISCONNECT GROUP 1 ELEMENT 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP
Detection'Group1'Element2'OBJECT_MULTI_STATE_OUTPUT:112;1211;T7_G0001_E02;14;112;CONNECT/DISCONNECT GROUP 1 ELEMENT 2;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP
Detection'Group3'Element1'OBJECT_MULTI_STATE_OUTPUT:114;1211;T7_G0002_E01;14;114;CONNECT/DISCONNECT GROUP 2 ELEMENT 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP
Detection'OBJECT_MULTI_STATE_OUTPUT:201;1211;T8_G0001_E00;14;201;COMMAND TO A PANEL;;;;;;;;;;;Command_Panel;Esser_EO_FI_CMDPAN
OBJECT_MULTI_STATE_VALUE:42;1211;T4_G0001_E00;19;42;PANEL;;;;;;;;;;;Panel;Esser_EO_FI_PAN
OBJECT_NOTIFICATION_CLASS:11;1211;TS-ES-NC;15;11;NOTIFICATION_CLASS;;;;;;;;;;;;Esser_EO_FI_NC
OBJECT_MULTI_STATE_VALUE:1;1211;COMMUNICATION;19;1;ESSER COMMUNICATION STATUS;;;;;;;;;;;Connection;Esser_EO_FI_CON
OBJECT_MULTI_STATE_VALUE:41;1211;T3_G0113_E00;19;41;LINE 256;;;;;;;;;;;Line;Esser_EO_FI_LN
OBJECT_MULTI_STATE_VALUE:43;1211;T5_G0001_E00;19;43;ACOUSTIC;;;;;;;;;;;Acustic;Esser_EO_FI_ACU
OBJECT_MULTI_STATE_VALUE:44;1211;T6_G0001_E00;19;44;UE;;;;;;;;;;;Acustic;Esser_EO_FI_UE