Honeywell Esser Integration

This integration permits the user to access objects from corresponding Honeywell Esser devices and monitor them from Desigo CC.

info

Safety functions

Observe all applicable standards for the country as well as regional or local regulations when integrating safety functions.

Dependencies

The Honeywell Esser extension is configured to depend on the following extension, which will be automatically added, if it is not already installed in the system, when the Honeywell Esser installation feature is selected:

info

To be able to work with EDE files, you must manually add the following extension:
- Desigo System (Core)

Engineering for Honeywell Esser Fire System

The Honeywell Esser fire system can be integrated into Desigo CC in one of the following ways:

Before performing the online discovery or offline configuration, a BACnet driver and network must be created.

Type of Configuration

Engineering

Advantage

Disadvantage

Online discovery

For online engineering, Desigo CC is connected to the devices and you perform an online discovery of project data.

  • You import the latest online configuration.
  • Extensive coordination with the project engineer is not required.
    NOTE: The following information must, however, be clarified in advance: PICS, device ID, device name, and UDP port.
  • Scanning the network can take quite a long time.
  • The hierarchical structure to be displayed in System Browser is not influenced.
  • Only Management View is generated in System Browser. Data is alphabetically displayed regardless of object type.

Offline import

For offline engineering, you must edit and import an Engineering Data Exchange (EDE). An online connection with the BACnet device is not required.

  • Engineering can take place in the office.
  • The following views are supported in System Browser:
    • Management View (generated automatically by the system).
    • Logical View (determined by the configuration file)
    • User View (only if already created in Desigo CC. It can then be set through the configuration file)
    • Graphic engineering can be completed in advance at the office.
  • Project data might not be up-to-date.
  • Requires more coordination to receive the EDE data from the project engineer.

Supported Object Types

Both online discovery and offline import support standard BACnet objects only. This means that BACnet extensions made by the manufacturer are not supported by these Desigo CC features. The current version supports the defined BACnet objects in the following library: Project > System settings > Libraries > Fire (HQ) > Devices > BACnet > Object models.

Object Models and Object Types in the Library Fire_Device_Esser_150_HQ_1

Object Model

Short Name

Full Name

GMS_BACnet_Esser_EO_FI_ACU_150

ACU

Acusting

GMS_BACnet_Esser_EO_FI_CMDPAN_150

CMDPAN

Command Panel

GMS_BACnet_Esser_EO_FI_CON_150

CON

Connection

GMS_BACnet_Esser_EO_FI_DISFP_150

DISFP

Disconnect Fire Point Command

GMS_BACnet_Esser_EO_FI_FP_150

FP

Fire Point

GMS_BACnet_Esser_EO_FI_GW_150

GW

Gateway

GMS_BACnet_Esser_EO_FI_LN_150

LN

Line

GMS_BACnet_Esser_EO_FI_NC_150

NC

Notification Class

GMS_BACnet_Esser_EO_FI_OUT_150

OUT

Output

GMS_BACnet_Esser_EO_FI_PAN_150

PAN

Panel

GMS_BACnet_Esser_EO_FI_UE_150

UE

UE

Supported EoTypes and Functions from EDE File

The EDE file contains a list of items where you can set a specific Function and EoType for fire objects.

See an example below. For details, see Honeywell Esser EDE File Formats.

#Engineering-Data-Exchange. Template example for ESSER integration;;;;;;;;;;;;;;;;;

VERSION_OF_LAYOUT;2;;;;;;;;;;;;;;;;

#mandatory;mandatory;mandatory;mandatory;mandatory;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional;optional

#keyname;device obj.-instance;object-name;object-type;object-instance;description;present-value-default;min-present-value;max-present-value;commandable;supports COV;hi-limit;low-limit;state-text-reference;unit-code;state-text;function;EoType

#;;;;;;;;;;;;;;;;;

# Parent Hierarchy levels;;;;;;;;;;;;;;;;;

Detection;1211;Esser'Detection;999;10002;Building;;;;;;;;;;;;Esser_EO_FI_AGG

Detection'Group1;1211;Esser'Detection'Group1;999;10003;Floor1;;;;;;;;;;;Automatic_Group;Esser_EO_FI_AGG

Detection'Group1'Element1;1211;Esser'Detection'Group1'Element1;999;10004;Room1;;;;;;;;;;;Automatic_Element;Esser_EO_FI_AGG

Detection'Group1'Element2;1211;Esser'Detection'Group1'Element2;999;10005;Room2;;;;;;;;;;;Automatic_Element;Esser_EO_FI_AGG

Detection'Group3;1211;Esser'Detection'Group3;999;10006;Floor3;;;;;;;;;;;Manual_Group;Esser_EO_FI_AGG

Detection'Group3'Element1;1211;Esser'Detection'Group3'Element1;999;10007;Room3;;;;;;;;;;;Manual_Element;Esser_EO_FI_AGG

Detection'Outputs;1211;Esser'Detection'Outputs;999;10009;Control Outputs;;;;;;;;;;;;Esser_EO_FI_AGG

#;;;;;;;;;;;;;;;;;

BACnet-ESSER;1211;BACnet-ESSER;8;1211;-;;;;;;;;;;;;Esser_EO_FI_GW

Detection'Group1'OBJECT_MULTI_STATE_VALUE:2;1211;T1_G0001_E00;19;2;GROUP 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP

Detection'Group3'OBJECT_MULTI_STATE_VALUE:4;1211;T1_G0003_E00;19;4;GROUP 3;;;;;;;;;;;FirePoint;Esser_EO_FI_FP

Detection'Group3'OBJECT_MULTI_STATE_OUTPUT:103;1211;T7_G0003_E00;14;103;CONNECT/DISCONNECT GROUP 3;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP

Detection'Group1'OBJECT_MULTI_STATE_OUTPUT:101;1211;T7_G0001_E00;14;101;CONNECT/DISCONNECT GROUP 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:22;1211;T2_G0011_E00;19;22;OUTPUT 11;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:23;1211;T2_G0012_E00;19;23;OUTPUT 12;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:24;1211;T2_G0013_E00;19;24;OUTPUT 13;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:25;1211;T2_G0014_E00;19;25;OUTPUT 14;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:26;1211;T2_G0015_E00;19;26;OUTPUT 15;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Outputs'OBJECT_MULTI_STATE_VALUE:27;1211;T2_G0016_E00;19;27;OUTPUT 16;;;;;;;;;;;Output;Esser_EO_FI_OUT

Detection'Group1'Element1'OBJECT_MULTI_STATE_VALUE:12;1211;T1_G0001_E01;19;12;GROUP 1 ELEMENT 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP

Detection'Group1'Element2'OBJECT_MULTI_STATE_VALUE:13;1211;T1_G0001_E02;19;13;GROUP 1 ELEMENT 2;;;;;;;;;;;FirePoint;Esser_EO_FI_FP

Detection'Group3'Element1'OBJECT_MULTI_STATE_VALUE:18;1211;T1_G0003_E01;19;18;GROUP 3 ELEMENT 1;;;;;;;;;;;FirePoint;Esser_EO_FI_FP

Detection'Group1'Element1'OBJECT_MULTI_STATE_OUTPUT:111;1211;T7_G0001_E01;14;111;CONNECT/DISCONNECT GROUP 1 ELEMENT 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP

Detection'Group1'Element2'OBJECT_MULTI_STATE_OUTPUT:112;1211;T7_G0001_E02;14;112;CONNECT/DISCONNECT GROUP 1 ELEMENT 2;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP

Detection'Group3'Element1'OBJECT_MULTI_STATE_OUTPUT:114;1211;T7_G0002_E01;14;114;CONNECT/DISCONNECT GROUP 2 ELEMENT 1;;;;;;;;;;;Disconnect_FirePoint;Esser_EO_FI_DISFP

Detection'OBJECT_MULTI_STATE_OUTPUT:201;1211;T8_G0001_E00;14;201;COMMAND TO A PANEL;;;;;;;;;;;Command_Panel;Esser_EO_FI_CMDPAN

OBJECT_MULTI_STATE_VALUE:42;1211;T4_G0001_E00;19;42;PANEL;;;;;;;;;;;Panel;Esser_EO_FI_PAN

OBJECT_NOTIFICATION_CLASS:11;1211;TS-ES-NC;15;11;NOTIFICATION_CLASS;;;;;;;;;;;;Esser_EO_FI_NC

OBJECT_MULTI_STATE_VALUE:1;1211;COMMUNICATION;19;1;ESSER COMMUNICATION STATUS;;;;;;;;;;;Connection;Esser_EO_FI_CON

OBJECT_MULTI_STATE_VALUE:41;1211;T3_G0113_E00;19;41;LINE 256;;;;;;;;;;;Line;Esser_EO_FI_LN

OBJECT_MULTI_STATE_VALUE:43;1211;T5_G0001_E00;19;43;ACOUSTIC;;;;;;;;;;;Acustic;Esser_EO_FI_ACU

OBJECT_MULTI_STATE_VALUE:44;1211;T6_G0001_E00;19;44;UE;;;;;;;;;;;Acustic;Esser_EO_FI_UE