S-Bus Integration
The S-Bus extension allows integrating S-Bus systems into Desigo CC via an adapter software.

The adapter is not part of the Desigo CC installation. After installation, the adapter installer package (SBus_Adapter_Setup.msi) is available in \GMSMainProject\AddSW\.
Once you install and start this software service, the adapter is ready to be executed and used in Desigo CC. For instructions, see Installing and Starting the S-Bus Adapter.
To integrate the S-Bus adapter, a SORIS driver and a SORIS network (monitored by one SORIS driver) must be created and configured. Once the adapter object is created, it starts automatically as a Windows service using the http or https protocol. You can also start the adapter manually:
- Using the http protocol (unsecure): double-click the executable SBus_Adapter.exe available in the file system with the installation.
- Using the https protocol (secure): enter
–secure:[thumbprint]
by command line.
For each adapter created, it is necessary to configure the URL IP address of the computer from which the network adapter is run.
For instructions, see Integrating S-Bus.
Dependencies
The S-Bus extension is configured to depend on the following extension, which will be automatically added, if it is not already installed in the system, when the S-Bus installation feature is selected:
- SORIS Driver (see SORIS)
- Building Automation Common