Configure the STT20 BACnet Time Synchronization
Fire events displayed on the management stations are time-stamped by the fire actuation panels. To avoid inconsistencies, the clock of the fire actuation panels must be aligned with the clock on any of the management stations.
- The management stations and the fire actuation panels are properly set to the same local time zone.
- In System Browser, select Project > Field Networks > [BACnet Network] > BACnet.
- Click one of the STT20 units.
NOTE: Only one unit must be synchronized. If you know which of the units is set as Global System Time master, select that unit.
- Click the BACnet tab and open the Timing and Status Info expander.
- In the Time sync type drop-down list, select UTC.
- In the UTC offset field, check that the value matches the time zone of the management station.
- The UTC offset value is acquired from the fire system. The UTC offset is expressed in minutes, with opposite sign (for example, if the UTC offset is +1 hour, it has to be expressed as -60). You can correct the UTC offset value offline in the fire system tool, then restart or reconnect the fire system, and check the new value acquired.
- (Optional) Adjust the time synchronization parameters in the BACnet driver:
- Depending on whether the driver runs (on the Server or FEP station), select one of the following:
- Project > Management System > Servers > Main Server > Drivers > [BACnet driver]
- Project> Management System > FEPs > [FEP] > [drivers folder] > [BACnet driver]
- Open the Time Synchronization expander, and configure the following:
- Time sync interval: Set the synchronization delay in minutes. Default is 1440 (24 hours).
- Align intervals: Select the check box to start the periodic time synchronization on the hour.
- Interval offset: Set a delay between the Time sync interval and the actual time sync.
- Click Save .