Prepare the STT Configuration in Cerloop

Configuring the NK823x Gateway

Before configuring the STT20 or STT11 Cerloop on Desigo CC, make sure to have configured the NK823x gateway on the BACnet network.
See the NK823x integration instructions.

Planning the BACnet Network

Define the unique BACnet address (Device ID) for all STT20/STT11/SK11 units in the Cerloop.

Exporting the STT Configuration Files

You can import the STTxx data structures into the Desigo CC project using the configuration files exported by the STTxx tool. The configuration files are text files (.TXT) that contain the complete data structure of the panels.

NOTICE
Incorrect Interpretation of Messages

After first import, if the panel configuration is modified, you will need to import the configuration file again to align Desigo CC. Failing to import the latest configuration file may result in an incorrect interpretation of field messages. An Unidentified event is generated in all cases when a message is received with no corresponding data point.