Synchronize the MK7022 Event Clock

To avoid inconsistencies in the events time stamp, you need to synchronize the MK7022 unit clock with Desigo CC.

  1. In System Browser, select Project > Field Networks > [BACnet network] > [Cerloop] > [MK7022 ] > [MK7022 Device].
  1. Select the BACnet tab.
  1. Open the Timing and Status Info expander.
  1. In the Time sync type drop-down list, select Local Time.
  1. In the UTC offset text field, type the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, type -60).
  1. Click Save .