Configure STT11 Fire Systems in the Cerloop

After configuring the Cerloop and MK7022 as above, you can add one or more STT11 fire systems under the Cerloop network.
Repeat the following procedures for each STT11 fire system.

Create the STT11 under Cerloop

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop].
  1. In the Cerloop tab, click New and select New STT11 System.
  1. In the New Object dialog box, enter a name and description.
  1. Click OK.
  • The new STT11 is added to System Browser.

Add the SK11 Gateway under the STT11

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop] > [STT11 system]
  1. In the Cerloop tab, click New and select New SK11.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The SK11 is added to System Browser, and automatically selected.
  1. In the Configuration expander, enter the Local address of the SK11 in the Cerloop, as configured in the fire system.
    NOTE: Valid values are: 110, 120, 130, 140, 210, 220, 230, 240, 800 to 862 (default: 110).
  1. Click Save .

Add STT11 panels under the STT11 Fire System

Repeat this procedure for all the STT11 panels you want to add.

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop] > [STT11 system].
  1. In the Cerloop tab, click New and select New STT11.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The newly created STT11 is automatically selected in System Browser.
  1. In the Configuration expander, enter the Local address of the STT11 in the Cerloop, as configured in the fire system.
    NOTE: Valid values are: 111 to 118, 121 to 128, 131 to 138, 141 to 148, 211 to 218, 221 to 228, 231 to 238 , 241 to 248 (default: 111).
  1. Click Save .