Configure STT20 Fire Panels in the Cerloop

Repeat this procedure for all the STT20 panels you want to add.

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop].
  1. In the Cerloop tab, click New and select New STT20.
  1. In the New Object dialog box, enter a name and description.
  1. Click OK.
  • The newly created STT20 is automatically selected in System Browser.
  1. In the Configuration expander, enter the following parameters:
  • Instance number: the BACnet Device Identifier.
  • Local address: STT20 address in the Cerloop. Valid values are: 111 to 118, 121 to 128, 131 to 138, 141 to 148, 211 to 218, 221 to 228, 231 to 238 , 241 to 248 (default: 111).
    NOTE: The Local Address must match the value set in the configuration file of the fire system.
  1. Click Save .