Synchronize the STT Events Clock
To avoid inconsistencies in the event time stamps, you must synchronize the Desigo CC clock with the NK823x Ethernet Port, and with all units configured in the fire system.
- Select Project > Field Networks > [BACnet network] > [Cerloop] > [STT20] > [STT20 Device] and perform the steps in Synchronize the Clock, below.
- Select Project > Field Networks > [BACnet network] > [Cerloop] > [STT11 System] > [SK11] > [SK11 Device] and perform the steps in Synchronize the Clock, below.
- Select Project > Field Networks > [BACnet network] > [Cerloop] > [STT11 System] > [STT11] > [STT11 Device] and perform the steps in Synchronize the Clock, below.
Synchronize the Clock
Perform these steps for each device node selected above.
- Click the BACnet tab.
- Open the Timing and Status Info expander.
- In the Time sync type drop-down list, select Local Time.
- In the UTC offset text field, type the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, type -60).
- Click Save .