Add the MK7022 Serial Interface to the Cerloop
If not already done, you need to create the MK7022 gateway in the Cerloop Network.
- Select Project > Field Networks > [BACnet Network] > [Cerloop].
- Select the Cerloop tab.
- Click New and select New MK7022.
- In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
- Click OK.
- The MK7022 is added to System Browser and automatically selected.
- In the Configuration expander of the Cerloop tab, enter the following parameters:
- Local Address: MK7022 address in the Cerloop. Valid values are 800 to 862 (default: 800).
- Baud rate: 1200 or 2400 (ISO1745).
- Click Save .