Set the Logical View for Maintenance
If the logical view is already present in the system, skip to step 7 in this procedure.
- From the System Browser drop-down list, select Management View.
- Select Project > System Settings > Views.
- The views workspace displays in the Views tab.
- In the View Name and View Description fields, enter a name and description for the logical view.
- In the Root node name and Root node description fields, enter a name and description for the root node of the logical view.
- From the Type drop-down list, select Logical.
- Click Save .
- The logical view object is added to System Browser under Views. Its name becomes available in the System Browser drop-down list.
- Display the [logical view] in the view builder workspace of the Views tab as follows:
a. From the System Browser drop-down list, select the [logical view].
b. In the System Browser tree, select the [logical view] root node.
- In the view builder workspace, populate the logical view with maintenance objects as follows:
a. select the [logical view] level.
b. Drag the maintenance objects (such as Electrical, HVAC and so on) that you want to link from System Browser to the appropriate level or sublevel under the [logical view] level.
c. Drag the Documents folder to the [logical view] level.
- Click Save .