Configure Web Rules for AIC Pharma Reports
- Trend Logs are available.
- System Manager is in Engineering mode.
- The default view is set to Show Description.
- Select Project > System Settings > Application Link Rules.
- The Rule Editor displays.
- Select the Rule Editor tab.
- Open the Trigger Conditions expander.
- In System Browser, select the Manual navigation check box.
- Drag a trend log object from any view in System Browser onto the Path area.
NOTE: You can select a parent folder to add more than one trend log to the report.
- From the menu that displays, select Add new elements and subtree.
- In the Output expander, from the Application drop-down list, select the required (AIC Pharma Report) application.
- The default AIC Pharma Reporting parameters display.
NOTE: You do not need to specify any values here. However, you must specify these values for a saved link to be executed through a reaction.
- Click Save As .
- In the Save As dialog box, enter a name and description.
- Click OK.
- The new web rule appears in the Application Link Rules folder.
- (Optional) Repeat the steps above to create additional web rules for other report types.