Check the Notification Class

In order to ensure a correct display on the Summary bar, the notification class must be properly set in the field network. Do this check for each individual data point as well as on the notification class (NC) object.

BACnetFireStandard_NC Alarm Table

Alarm class

Event state

Alarm priority

Fault

Fault (1)

n/a

Life Safety

n/a

0‒31

Imminent Danger

n/a

32‒63

Fault

n/a

64-95

Fault

n/a

96-127

Anomaly

n/a

128‒191

Information

n/a

192‒255

 

Some field networks automatically calculate the notification class from the alarm function and alarm class. In this case, you cannot edit the notification class on the alarm object. Change the alarm function or alarm class to get another notification class.