Check the Notification Class
In order to ensure a correct display on the Summary bar, the notification class must be properly set in the field network. Do this check for each individual data point as well as on the notification class (NC) object.
BACnetFireStandard_NC Alarm Table | ||
Alarm class | Event state | Alarm priority |
Fault | Fault (1) | n/a |
Life Safety | n/a | 0‒31 |
Imminent Danger | n/a | 32‒63 |
Fault | n/a | 64-95 |
Fault | n/a | 96-127 |
Anomaly | n/a | 128‒191 |
Information | n/a | 192‒255 |
Some field networks automatically calculate the notification class from the alarm function and alarm class. In this case, you cannot edit the notification class on the alarm object. Change the alarm function or alarm class to get another notification class.