(Optional) Assign a New Alarm Table
To assign a new alarm table to a property of a device (and to the corresponding property of the child data points that are set to apply the default alarm table), proceed as follows.
- Select Project > Field Networks > [network name] > [device].
- In the Object Configurator tab, open the Properties expander.
- Select the Alarm.OffNormal property or another alarm property.
- In the Alarm Configuration expander, select the Valid check box.
- The check mark changes from blue (defined in the object model) to gray (defined at instance level).
- Select the Field System option and then the corresponding Alarm Table from the drop-down list.
- (Optional) Repeat the assignment of a new alarm table for all the required devices.
- You can assign the new alarm table to other types of data points as necessary. In a similar way, to assign the alarm table also to all data points of the same type, do the following:
a. Double-click the Object Model label to access the object model node.
b. Select the Models & Functions tab.
c. Assign the new alarm table to the Alarm.OffNormal property of the object model.