Add the CK11 Gateway

You can skip this step for CC11 EP5.

  1. Select Project > Field Networks > [BACnet Network] > [CS11].
  1. Select the CS11 tab.
  1. Click New and select New CK11.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The newly created CK11 is automatically selected in System Browser.
  1. In the Configuration expander, enter the following parameters:
  • Instance number: the BACnet Device Identifier.
  • Local address: CK11 address, as configured in the fire system.
    NOTE: Valid values are: 110, 120, 130, 140, 210, 220, 230, 240, 800 to 862 (default: 110).
  • Vitality check enabled: automatically selected.
    NOTE: Enabling the vitality check is mandatory, to correctly diagnose communication problems.
  • Vitality timeout (sec): the maximum tolerated delay of the heartbeat message sent by the Gateway name (30 to 999 seconds; default: 50).
    NOTE: The vitality timeout must be greater than the heartbeat message interval.
  • Protocol type: ISO1745 (default) or Cerban.
  • Baud rate: 1200 or 2400 (ISO1745), 300 or 600 (Cerban).
  1. Click Save .