Configure the NK823x Time Synchronization
Configure the NK823x Events Clock Synchronization
To avoid inconsistencies in the events time stamp, do this procedure to synchronize the NK823x clock with Desigo CC.
- In System Browser, select Project > Field Networks > [BACnet network] > [NK823x] > [NK823x Device].
- Select the BACnet tab.
- Open the Timing and Status Info expander.
- In the Time sync type drop-down list, select Local Time.
- In the UTC offset field, enter the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, type -60).
- Click Save .
(Optional) Configuring BACnet Driver Time Synchronization
- Depending whether the driver runs on the Server or FEP station, select one of the following:
- Project > Management System > Servers > Main Server > Drivers > [BACnet driver]
- Project > Management System > FEPs > [FEP] > [Drivers Folder] > [BACnet driver]
- Open the Time Synchronization expander, and configure the following:
- Time sync interval (minutes): Set the synchronization delay in minutes. Default is 1440 (24 hours).
- Align intervals: Select the check box to start the periodic time synchronization on the hour.
- Interval offset: Set a delay between the time sync interval and the actual time sync.
- Click Save.