Add MK7022 to Cerloop for CS11

If not already done, you need to create the MK7022 gateway in the Cerloop Network.

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop].
  1. Select the Cerloop tab.
  1. Click New and select New MK7022.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The MK7022 is added to System Browser and automatically selected.
  1. In the Configuration expander of the Cerloop tab, enter the following parameters:
    - Local Address: MK7022 address in the Cerloop. Valid values are 800 to 862 (default: 800).
    - Baud rate: 1200 or 2400 (ISO1745).
  1. Click Save .