Synchronize MK7022 Event Clock for CS11

To avoid inconsistencies in the events time stamp, you need to synchronize the MK7022 unit clock with Desigo CC.

  1. In System Browser, select Project > Field Networks > [BACnet network] > [Cerloop] > [MK7022 ] > [MK7022 Device].
  1. Select the BACnet tab.
  1. Open the Timing and Status Info expander.
  1. In the Time sync type drop-down list, select Local Time.
  1. In the UTC offset text field, type the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, type -60).
  1. Click Save .