Configure CS11 System under Cerloop

After configuring the Cerloop and MK7022 as above, you can add one or more CS11 fire systems under the Cerloop network. Repeat the following steps 6a, 6b and 6c below for each CS11 fire system.

Create the CS11 under Cerloop

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop].
  1. Select the Cerloop tab.
  1. Click New and select New CS11.
  1. In the New Object dialog box, enter a name and description.
  1. Click OK.
  • The new CS11 is added to System Browser.

Add the CK11 Gateway Under the CS11

You can skip this step for CC11 EP5.

  1. Select Project > Field Networks > [BACnet Network] > [Cerloop] > [CS11].
  1. In the CS11 tab, click New and select New CK11.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The CK11 is added to System Browser, and automatically selected.
  1. In the Configuration expander, enter the following parameters:
  • Instance number: the BACnet Device Identifier.
  • Local address: CK11 address in the Cerloop, as configured in the fire system.
    NOTE: Valid values are: 110, 120, 130, 140, 210, 220, 230, 240, 800 to 862 (default: 110).
  1. Click Save .

Add CC11/CI11 Panels under the CS11 Fire System

Complete this procedure for all the CC11 or CI11 panels you want to add.

  1. In System Browser, select Project > Field Networks > [BACnet Network] > [Cerloop] > [CS11].
  1. In the CS11 tab, click New and select New CC11/CI11.
  1. In the New Object dialog box, enter a name and description, and the Instance number: the BACnet Device Identifier.
  1. Click OK.
  • The newly created CC11/CI11 is automatically selected in System Browser.
  1. In the Configuration expander, enter the following parameters:
  • Instance number: the BACnet Device Identifier.
  • Local address: CC11/CI11 address in the Cerloop, as configured in the fire system.
    NOTE: Valid values are: 111 to 118, 121 to 128, 131 to 138, 141 to 148, 211 to 218, 221 to 228, 231 to 238 , 241 to 248 (default: 111).
  • Ack mode: Always general ACK (a single acknowledgment command affects all pending events) or Single event ACK (a separate acknowledgment command is required for each pending event).
  1. Click Save .