Synchronize CK11 Event Clock in Cerloop
To avoid inconsistencies in the events time stamp, you need to synchronize the CK11 unit clocks with Desigo CC. Repeat the below procedures for all the CK11 units in the configuration.
- In System Browser, select Project > Field Networks > [BACnet Network] > [Cerloop] > [CS11] > [CK11] > [Device CK11].
- Select the BACnet tab.
- Open the Timing and Status Info expander.
- In the Time sync type drop-down list, select Local Time.
- In the UTC offset field, enter the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, enter -60).
- Click Save .