Source Meter

Source Meter (Optional)

Name

Description

Metering Point

Property of a meter device or an online/offline trend log that collects the property values of the meter device.
NOTE:
This value needs to represent an energy or volume or another accumulation measurement in general, not a rate of change measurement like Power or Flow.

Meter Synchronization

Media Unit (input)

Unit of measurement for the selected media unit for the second meter.

Report Unit (output)

The required unit of measurement for the selected media unit in a report that contains data from the second meter. This unit can be identical to or different from the unit specified in the Media Unit field.

Offset

Value that must be specified to the second managed meter every time after a rollover in order to arrive at the exact meter reading.

Notification Profile

Notification profile associated with the second managed meter.

Max Meter Reading

Maximum meter reading value of the second managed meter.

This is an optional field. If the maximum meter reading is not specified, then the maximum limit of the GMSreal type shall be considered as the maximum meter reading for the purpose of setting the warning limits for a meter rollover.