Run the Network Scan
Restriction that applies when running the device discovery
Only standard BACnet objects are supported. Proprietary object and object extensions are lost.
- In System Browser, select Project > Field Networks > [Network name].
- Select the Discovery tab.
- Open the Hierarchies Mapping expander.
- Select the logical hierarchy and drag the top node to the column Import this hierarchy under this node.
- Click Save .
- Open the Discovery Settings expander.
- In the Scan timeout in seconds field, set the maximum time for scanning devices (the default value is 60 seconds).
NOTE: If the Enable auto-discovery of devices option is selected, the scanned devices are immediately imported into the project database.
- Select and configure one of the following filter options.
NOTE: The discovery function scans the entire BACnet network for BACnet devices. To avoid impairing the network unnecessarily, it is recommended to apply one of the available filters.
- Use network filter and enter the Network number filter.
- Use instance filter and enter the Beginning instance and Ending instance (object-identifier).
- Use vendor filter and enter a Vendor ID.
NOTE: The SecuriFire vendor identifier is 309.
- Click Save .
- Click Scan.
- While devices are discovered, in the Network Scan section of the Device Discovery expander, the Library column will display the Family:SubFamilyName of the discovery rules, whose library will be used to create the instances. In this case, SecuriFire:Fire.
NOTE: To stop the network scan, clear all check boxes, and click Save .