Configure SI400 in the Management Station

Repeat this procedure for each SI400 panel you want to configure.

  1. Select Project > Field Networks > [BACnet Network].
  1. Select the Object Configurator tab.
  1. Click New and select New SI400.
  1. In the New Object dialog box, enter a name and description.
  1. Click OK.
  • The new SI400 is added to System Browser and automatically selected.
  1. Select the SI400 tab.
  1. In the Configuration expander, enter the Instance number: the BACnet Device Identifier.
  1. Click Save .
  1. In System Browser, depending on the SI400 serial line connection to the NK823x, select one of the following:
    - Project > Field Networks > [BACnet Network] > [NK823x] > [COM1]
    - Project > Field Networks > [BACnet Network] > [NK823x] > [COM2]
    - Project > Field Networks > [BACnet Network] > [NK823x] > [Expansion Board] > [COM3]
    - Project > Field Networks > [BACnet Network] > [NK823x] > [Expansion Board] > [COM4]
    NOTE:
    If COM 3 or COM 4 is used, you need to configure the NK823x expansion board.
  1. Select the NK8000 tab.
  1. In the Configuration expander, from the Control Unit drop-down list, select the SI400 you configured previously.
  1. Click Save .