Synchronize SI400 Events Clock

To avoid inconsistencies in the events time stamp, you must synchronize the SI400 unit clocks with Desigo CC.

  1. In System Browser, select Project > Field Networks > [BACnet Network] > [SI400] > [Device SI400].
  1. Select the BACnet tab.
  1. Open the Timing and Status Info expander.
  1. In the Time sync type drop-down list, select Local Time.
  1. In the UTC offset field, enter the UTC offset in minutes, with opposite sign (for example, if the UTC offset is +1 hour, type -60).
  1. Click Save .
  1. Repeat the steps above for all other SI400 units.