STT FCnet/SAFEDLINK Architecture
STT20: FCnet/SAFEDLINK Architecture
STT20 panels are networked together with an FS20 fire detection system on an FCnet/SAFEDLINK network. One of the fire actuation units acts as a Global Access Point (GAP) and handles the BACnet communication to Desigo CC.
Each networked STT20 panel must be equipped with an FCGW20-2 gateway.
STT20 on FCnet - System Limits and Compatibility
System limits:
- 10 STT20 and 12 fire detection panels per SAFEDLINK fire network.
Compatibility information:
- STT20 panel version: 5.21.xx and newer.