Configure a Customized Video Alarm Table
This procedure is part of the workflow for customizing Video alarm tables.
Create a Customized Video Library
Skip this section if the customized video library already exists.
- In System Browser, select Project > System Settings > Libraries > L1 Headquarters > Video > Video.
- Select the Library Configurator tab.
- Click Customize the entire library to a lower level .
- Click OK.
- The structure of the video library is duplicated under the allowed customization level. For example, […] > L4-Project > Video > Video.
Copy the Headquarters Video Alarm Table to the Customized Library
Skip this section if the alarm table you want to modify already exists in the customized video library.
- In System Browser, under Project > System Settings > Libraries > L1 Headquarters > Video > Video > Alarm Tables >, select the alarm table you want to customize:
- Alarm Table Generic Events
- Alarm Table Analytic Events
- Click Save as .
- In the Save Object As dialog box, as the destination location, select the Alarm Tables block of the customized video library. For example, […] > L4-Project > Video > Video > Alarm Tables.
- Enter a name and description for the customized video alarm table. Choose a name/description that will make it easy to distinguish this alarm table from the headquarters one.
- Click OK.
- A copy of the Headquarters video alarm table is added under the Alarm Tables block of the customized library.
Modify the Video Alarm Table in the Customized Library
- Select the alarm table in the customized video library. For example, […] > Libraries > L4-Project > Video > Video > Alarm Tables > [alarm table].
- In the Object Configurator tab, open the Alarm Configuration expander.
- The content of the video alarm table displays.
- In the Event Type column, locate and select the event you want to modify.
- In the selected event you can:
- In the Alarm Class column, modify the category of the event. In general, the alarm classes correspond to the event lamps of the Summary bar.
- In the Skip Alarm Generation column, choose True to disable the event generation or choose False to enable it.
NOTE: Do not modify any other column in the generic events alarm table. If you are instead working on the analytic events alarm table, see also Customizing VMS Analytic Events for a specific example.
- Click Save .
- The modified alarm table is available. You can now apply it to a customized video object model.