Commend Troubleshooting

This section covers several areas of troubleshooting.

Troubleshooting SORIS

In SORIS, see SORIS Troubleshooting.

Troubleshooting OPC UA

In OPC UA, see OPC UA Client Troubleshooting.

Troubleshooting Connection Problems

Problem

Situation

Do the following...

OPC UA adapter cannot establish a secure connection with the OPC server. The following error occurs:

Error establishing a connection: Could not send an Open Secure Channel request.

The adapter cannot retrieve the certificates to connect to the OPC server. The user who activates the OPC UA Adapter as a service is different from the one who generated the application certificate.