Settings for Global AIC Pharma Reports

In the Advanced Reporting configuration page, you can set the following global settings for AIC Pharma reports.

Name

Default

Function

Reports

Value format display

##0.00

Set the format of analog value in different reports.

All

Default High limits value

100

This is the default value displayed in the Trend Chart report dialog.

Trend Aggregated Table Report, Custom Statistic Summary Report 1

Default Low limits value

0

This is the default value displayed in the Trend Chart report dialog.

Trend Aggregated Table Report, Custom Statistic Summary Report 1

Date Format

Auto

Set the format of the time.

For example: dd:MM:mm:ss.SSS

Custom Statistic Summary Report 1

Display the number of records

True

Enable/disable in the display of the number of records in the header of the Statistic Summary report.

Custom Statistic Summary Report 1

Format used for Object Description

Description

Set the description format of a datapoint if the following are used:

  • Point description
  • Point name
  • Point Alias (If it is not defined, the description is used.)

Custom Statistic Summary Report 1

Ignore the Time Shift in Trend Series

True

Ignore the time shift event in different reports. Time shift can be associated with the high or low value, which can influence the calculation or display.

Custom Statistic Summary Report 1

Activation Energy for MKT (kJ/mole)

83.144

Enter the activation energy for the product or substance being monitored. The available range is from 50 to 200. If the activation energy is not known, use the default value is used, which is a standard default for a wide range of pharmaceutical products

Custom Statistic Summary Report 1

Search Period Before Selected Time (Hours)

5

Set the number of hours to search for calculations before the start date/time of the report.

Custom Statistic Summary Report 1