PAC2200CLP
The PAC2200CLP (Certified Load Profile) is a power monitoring device for measuring, monitoring, calculating, displaying and archiving all the relevant line parameters. It collects all the basic measured variables. Limit values are available for line monitoring. It is integrated with quarter hour load profile with a memory depth for billing all relevant data. It performs single-phase, two-phase, or three-phase measurement and can be used in two-wire, three-wire, or four-wire TN, TT, and IT systems. The PAC2200CLP with multi-range power supply can thus be connected directly to every low-voltage system up to a line voltage of 690 V.
Connect PAC2200CLP power monitoring device to powermanager through the integral Ethernet interface using Modbus TCP.
Feature | Applicable |
Digital Inputs | Yes |
Digital Outputs | Yes |
Counters | Yes |
Synchronization | Yes |
Event Memory | Yes |
Power Period | Yes |
Power Quality | No |
N conductor | No |
Password | Yes |
TCP | Yes |
RTU | No |
Web page | Yes |
Counters and average power demand values
- Recording of active, reactive and apparent energy by means of several energy counters.
- Calculation and storage of the last demand period average value for active and reactive power for simple software-driven generation of load profiles.
- Calculation of average values for active and reactive power of the last completed demand period for import and export.
- Time stamp of the current demand period acc. to ISO8601 (local and UTC time).
- MID-certified active energy counter for import and export (Measuring Instruments Directive 2014/32/EU).
- With load profile measurement conforming to statutory calibration regulations and national approval according to PTB-A 50.7.
- Integrated 15-minute load profile memory with a storage depth for all billing-relevant data over 2 years.
- Integrated 15-minute load profile memory with a storage depth for all billing-relevant data over 2 years.
Features Specific to the Device:
- PAC2200CLP Device also supports the Field System Alarm. The events from PAC2200CLP is sent to powermanager as field alarm. The classes of alarm is medium.
- When the alarm is displayed in the Events tab, an option to acknowledge the alarm is provided along with the event and the source status, and once the user acknowledges the alarm, it will be removed from the event list. None of the events will be removed from the device and remain in the device memory.