Measurement Points Expander

Allows you to configure the measurement point settings in the powermanager system. It consists of the following columns:

  • Group: Displays the category of the measurement point. You can select the measurement point category from the dropdown box.
  • Measurement Point: Displays the name of the measurement point. You can select the measurement point from the dropdown box.
  • Unit: Displays the unit of the measurement point.
  • Poll: Select the checkbox for the measurement point to be polled.
  • Display: Select the checkbox for the measurement point to be displayed in the Measurement values tile in the Overview tab in Operating mode.
  • Archive: Select the checkbox for the measurements points for which data has to be archived.
  • Alarm: Select the checkbox to enable alarms for the corresponding measurement points.

Alarm Configuration Expander

To configure a workstation alarm for a point, you must configure the following fields:

  • Alarm kind: Allows you to choose the type of alarm to be activated.
  • Reset: Allows you to rest all alarm conditions from the table and reset the default alarm class.
  • Alarm Type: The alarm type to be enabled for an event.
  • Check Acknowledgement checkbox.
  • For Range:
    Priority: Low, Medium, High and Fault
    Operator:: In range, !.. : Not in range , || : OR, !|| : NOR
    Range: The value, or range of values, for which an alarm is to be issued.
  • For Limit:
    Priority: Low, Medium, High and Fault
    Check Acknowledgement checkbox.
    Operator: : > : Greater than , >= : Greater than or equal to , < : Less than, <= : Less than or equal to
    Limit: User defined values
    Operator: Allows you to select between the = and None options.
    UpperHysteresis: The upper range for the alarm value beyond which alarms will be generate.
    Operator: Allows you to select between the = and None options.
    Lower Hysteresis: The lower range for the alarm value below which alarms will be generated.
  • EventText: The text to display when the alarm is issued.
  • NormalText: The text to display when the alarm ceases.
  • New: Allows to add new rows with default alarm class and values.
  • Delete: Allows you to delete the selected alarm row.

NOTE:
PAC4200 device type supports the Field System Alarm function. See PAC4200 for more information.