Measurement Points Expander
Allows you to configure the measurement point settings in the Powermanager system. It consists of the following columns:
- Group: Displays the category of the measurement point. You can select the measurement point category from the drop-down box.
- Measurement Point: Displays the name of the measurement point. You can select the measurement point from the drop-down box.
- Unit: Displays the unit of the measurement point.
- Poll: Select the checkbox for the measurement point to be polled.
- Display: Select the checkbox for the measurement point to be displayed in the Measurement values tile in the Overview tab in Operating mode.
- Archive: Select the checkbox for the measurements points for which data has to be archived. This enables to store the value of measurement point in database. The database can be selected in Object Configurator tab > Properties.
NOTE: The Archive function stores the value of the selected measurement point in the History database. - Alarm: Select the checkbox to enable alarms for the corresponding measurement points.
Alarm Configuration Expander
To configure a workstation alarm for a point, you must configure the following fields:
- Alarm kind: Allows you to choose the type of alarm to be activated.
- Reset: Allows you to rest all alarm conditions from the table and reset the default alarm class.
- Alarm Type: The alarm type to be enabled for an event.
- Check Acknowledgement checkbox.
- For Range:
Priority: Low, Medium, High and Fault
Operator:: In range, !.. : Not in range , || : OR, !|| : NOR
Range: The value, or range of values, for which an alarm is to be issued. - For Limit:
Priority: Low, Medium, High and Fault
Check Acknowledgement checkbox.
Operator: : > : Greater than , >= : Greater than or equal to , < : Less than, <= : Less than or equal to
Limit: User defined values
Operator: Allows you to select between the = and None options.
UpperHysteresis: The upper range for the alarm value beyond which alarms will be generate.
Operator: Allows you to select between the = and None options.
Lower Hysteresis: The lower range for the alarm value below which alarms will be generated. - EventText: The text to display when the alarm is issued.
- NormalText: The text to display when the alarm ceases.
- New: Allows to add new rows with default alarm class and values.
- Delete: Allows you to delete the selected alarm row.


NOTE:
PAC4200 device type supports the Field System Alarm function. See PAC4200 for more information.