Comark Monitor Card Driver Management

Selecting the Comark Monitor Card node in System Browser, the Operation tab displays the Manager Status property and the associated Start and Stop commands.

Start/Stop Commands for Comark Card Driver

Manager Status and Commands

Manager Status

When the Comark card driver…

Available Command

Stopped

Is not running.

Start

Started

Starts and is properly running.

Stop

Failed

Starts, but there is no connection to the station (for example, station not reachable or disconnected).

Stop

Technical Notes

  • If you try to start the Comark driver with an invalid or incomplete configuration or the hosting station is not reachable, the Manager Status property of the driver becomes Failed, and a Fault event is generated.
  • If the station is disconnected, the Manager Status property becomes Failed, and a Trouble event is generated.
  • When the Manager Status property is Failed, you cannot modify the configuration (import operations are not allowed).
  • It is not possible to stop the Comark driver during import operations.
  • After configuring the Comark Card, power down the station and disconnect the power plug for at least 3 minutes to allow for a complete capacitor discharge. After that, reconnect power, restart the station, and check that the Comark card runs properly.