Migrate from SX Open to the Management Platform
Scenario
Integrating OPC data points without the existing Gateway SX Open. The current OPC Excel worksheet is required to process. For background information, see the reference section.
Prerequisites
- The OPC DA Discovery and Scripts extension modules are installed and assigned to the project.
- The following applies to all steps performed in Desigo CC:
- System Manager is in Engineering mode.
- The System Browser is in Management View.
Overview
1 | Create Conversion File |
To speed configuration, make sure the Desigo CC Transaction Mode is set to Simple
or the Automatic Switch of Transaction Mode is set to True
.
The automatic switch setting is recommended. Without it, to re-enable the logs, you need to set the Transaction Mode to Logging
at the end of the configuration procedure.