Integrating an SPC Intrusion System

This section provides a workflow for configuring Desigo CC to connect to SPC intrusion panels. For background information, see the reference section.

 

Prerequisites

  • The Desigo CC Intrunet SPC extension is installed and included in the active project.
  • The SPC panels are already installed and configured. For more information about the SPC configuration tools, see the separate SPC panel documentation.
  • You prepared the SPC configuration files for the panels and noted the values of RCT ID and RCT Port (for FlexC protocol).
  • System Manager is in Engineering mode.
  • System Browser is in Management View.

 

Overview

1
2
3
4
5
6

Create an SPC Network
Configure the SPC Driver
Associate the SPC Driver to a Panel
Import the SPC Panel Configuration File
Check SPC Panel Settings
Finishing Steps After SPC Import

 

 

NOTICE
Incorrect Interpretation of Messages

After first import, if the panel configuration is modified, you will need to import the configuration file again to align Desigo CC. Failing to import the latest configuration file may result in an incorrect interpretation of field messages. An Unidentified event is generated in all cases when a message is received with no corresponding data point.