Setting the Zone State Filter
To avoid excessive log data, you want to exclude notifications relating to physical state changes of inputs (for example, changes of the state of infrared intrusion detectors) from being sent to the management platform, when the corresponding area is unset.
- Desigo CC is configured to connect to an SPC intrusion system.
- System Manager is in Engineering mode.
- System Browser is in Management View.
- In System Browser, select Project > Field Networks > [SPC network] > [SPC panel].
- Select the SPC tab.
- Open the Zone State expander.
- Select the Zone state filter check box.
- Click Save .
- If the panel is connected (the configuration file is imported and the driver was started in full mode), you must stop and start its driver again to apply the new setting. See Stopping and Starting the SPC Driver.