In the Object Configurator tab, click New and select New Comark Driver. NOTE: You can only create one Comark driver on a station.
In the New Object dialog box, enter a name and description.
Click OK.
The newly created Comark node is automatically selected in System Browser.
In the System Management tab, open the General Settings expander.
(Optional) In the Vendor and Type field, enter a textual comment of your choice about the installed monitor card. By default, this field just indicates Comark.
In the Communication Port field, select the serial port connected to the card.
Click Save.
In the Properties expander, configure the relay output. The general procedure is the following: a. Select the Relay Active property. b. Drag a point from any of the System Browser views onto Data PointName. c. Enter the Property Name and Activation value. d. Click Save. e. Repeat the steps for all the data points to set. NOTE: The configuration of specific applications of the relay output is provided in the next sections.
Modify the default setting of one or more of the following properties: For each of the properties, select it, modify the value, and click Save.
Fan Alarm (mandatory)
Set Alarm Timeout
Set High Limit In
Set Low Limit In
Set Message Interval
Sound Audible (mandatory)
Temperature Alarm
In the Operation tab, select the Manager Status property.