Import the Siport Configuration File
This procedure is part of the workflow for integrating a SiPort Modbus system.
Prerequisites
- You prepared the CSV file and applied the required Siport settings.
- You configured the modbus driver and network for Siport.
Import the CSV Configuration File
- The CSV file to import is available locally or over the network.
- To speed configuration, make sure the Desigo CC Transaction Mode is set to
Simple
.
- Select Project > Field Networks > [SIPORT network].
- In the Import tab, click Browse and select the configuration file.
- The Source Items list populates with the items you can import.
- (Optional) Open the Hierarchies Mapping expander if you want to link one or more data structures of the configuration file to the optional views:
a. In System Browser, select the optional view (for example, Logical View or Physical View).
b. Drag-and-drop the node of the optional view you want to link as root node into an available data structure listed in the Hierarchies Mapping expander.
NOTE: The Hierarchies Mapping configuration cannot be modified after the import.
- In the Source Items list, click and then click Import.
- The configuration data is available in System Browser.
- The Import Log button becomes available to show the import log.
- When finished, to resume normal operational monitoring, make sure the Transaction Mode is set back to
Logging
.
In case of problems, see the troubleshooting section.
NOTICE
Incorrect Interpretation of Messages
After first import, if the panel configuration is modified, you will need to import the configuration file again to align Desigo CC. Failing to import the latest configuration file may result in an incorrect interpretation of field messages. An Unidentified event is generated in all cases when a message is received with no corresponding data point.