Apply Alarm Table to Video Object Model

This procedure is part of the workflow for integrating video surveillance.

 

Prerequisites

 

Apply the Customized Alarm Table to a Customized Object Model

  1. In System Browser, select Project > System Settings > Libraries > L1 Headquarters > Video > Video > Object Model > Management.
  2. In the Models & Functions tab, click Customize .
    NOTE: If the icon is dimmed it means that the selected video object model is already customized. Skip to step 4.
  3. Click OK.
  4. The customized Management object model is added to the customized video library.
  5. In System Browser, select the customized Management object model. For example, […] > Libraries > L4-Project > Video > Video > Object Model > Management.
  6. In the Models and Functions tab, open the Properties expander.
  7. In the property list, do one of the following, depending on which type of alarm table you want to apply:
    • To apply a customized Alarm Table Generic Events, select the EventsCollector property
    • To apply a customized Alarm Table Analytic Events, select the AnalyticEventsCollector property
  8. In the Alarm Configuration expander, from the Alarm table reference drop-down list, select the customized video alarm table you want to apply.
    NOTE: The list will show the alarm tables from all library levels, including L1-Headquarters, so be sure to select the alarm table that you customized to your level.
  9. Click Save .
  10. Stop and restart the Desigo CC project for the customization to take effect.