Integrating CS11 Systems in Cerloop

Scenario

You want to configure one or more CS11 fire systems in a Cerloop network, integrated into Desigo CC via NK823x on a BACnet network.
For background information, see the reference section.

Prerequisites

  • The Legacy systems via NK8000 extension is installed and included in the active project.
  • You have completed the following workflows:
  • You have defined the unique BACnet address (Device ID) for all CS11/CK11 units.
    See BACnet Networks for NK823x DMS Applications
  • From the AlgoWorks tool, you have exported the configuration files.
    The configuration files are text files (.txt) that contain the complete data structure of the panels.
  • System Manager is in Engineering mode.
  • System Browser is in Management View.

Overview

1
2
3
4
5
6
7
8

Create Cerloop Network for CS11
Add MK7022 to Cerloop for CS11
Synchronize MK7022 Event Clock for CS11
Connect MK7022 to NK823x for CS11
Configure CS11 System under Cerloop
Import CS11 Configuration File in Cerloop
Synchronize CK11 Event Clock in Cerloop
Download CS11 Configuration to NK823x in Cerloop